What are the design requirements of the transformer tank?
The design requirements of the transformer tank mainly include the following aspects:
1. Pressure sealing and pressure deformation test
Transformer tank should be able to pass the pressure sealing test, the specific requirements include different capacity of the transformer to withstand different test pressure, for example, 315kVA and the following transformer should withstand the test pressure of 20kpa, and 400kVA and above transformer should withstand the test pressure of 15kpa, after 12 hours should be no leakage.
For the pressure deformation test, different capacity transformers have different test pressure, for example, 315kVA and the following transformer test pressure is 25kpa, 400kVA and above transformer test pressure is 20kpa, after 5 minutes there should be no damage and there should be no impermissible permanent deformation.
2. Mechanical strength test
Transformer tank should be able to withstand a certain degree of mechanical pressure, for example, in the transformer tank to apply 103kpa positive pressure (hydraulic), after 10 minutes, the tank should not appear cracking phenomenon.
3.Transport impact test
Transformer tank should be able to resist the transport process of impact, the specific test methods and requirements by the user and the manufacturer to determine the consultation.
4. Anti-magnetic shielding and electric shielding
Transformer tank internal anti-magnetic shielding measures should be taken to reduce stray loss. Magnetic shielding should be fixed and insulation should be good, to avoid overheating or discharge caused by poor contact. Various types of electric shielding should be conductive and reliable grounding, to avoid suspended discharge or affect the dielectric loss of the winding.
5. Drainage of water and gas accumulation
The top of the tank should be sloped to allow for water drainage and gas build-up to the gas relay. All openings in the top of the tank shall have raised flanges, and wherever a gas pocket can be created, a bleeder plug shall be provided at the highest point thereof and connected to a utility line to route gas pooling to the gas relay.
6. Base and towing device
The exterior of the transformer tank floor shall be provided with a channelised steel base to allow the transformer to be towed along its long and short axes, and the base shall be equipped with the necessary towing devices.
These design requirements ensure the safety and reliability of the transformer tank when subjected to various stresses and environmental factors.