What Are The Alphanumeric Codes In The Transformer Model?

May 28, 2025

Leave a message

What Are The Alphanumeric Codes In The Transformer Model?

          In Shandong, a substation expansion project, engineers found two nominal same type of transformer actual parameter differences of up to 15% - the root cause of this oolong event, is actually a letter in the model code misunderstanding. Transformer model as the genetic code of power equipment, each character is hidden mystery.

I. Alphabetical sequence: structure code

      The first letter reveals the core features:

          - S: three-phase (Single-phase is D)

          - C: epoxy resin casting (oil-immersed with J for tank)

          - B: foil winding (omitted for cylindrical winding)

          - Z: on-load voltage regulation (no symbol for unexcited voltage regulation)

      Take SCB12-800/10 for example:

          - SCB: three-phase epoxy cast foil winding

          - 12: 12th generation design

          - 800: rated capacity 800kVA

          - 10: high voltage side voltage 10kV

      Special suffix concealed function:

          - N: indoor type (W for outdoor)

          - F: Protective type (IP23)

          - R: Rolled iron core structure

          - H: fire-resistant type (temperature-resistant grade upgraded)

II. Numerical Matrix: Performance Coordinates

      Accurate correspondence between capacity and voltage:

          - Digits before slash: Rated capacity (kVA)

          - Digits after slash: voltage level of high voltage side (kV)

          - Implicit parameter between slashes: LV side voltage usually defaults to 0.4kV

      Technical iteration in the design sequence number:

          - S11: 11th generation oil-immersed (no-load loss reduced by 30% compared with S9)

          - SCB14: amorphous alloy core (70% reduction in no-load current)

          - SH15: three-dimensional rolled iron core (8dB noise reduction)

      Environmental adaptability code:

         - TH: hot and humid type (humidity ≤95%)

         - TA: Dry heat type (altitude 2000m)

         - G: High altitude type (4000m working condition)

III. Special Symbols: Function Key

      Cooling Mode Code:

          - AN: Natural air-cooled (no fan required)

          - AF: Forced air-cooled (fan start-up temperature 65°C)

          - ONAN: Oil-immersed self-cooling (oil temperature limit 95°C)

      Insulation system marking:

          - F: heat-resistant 155°C (Class B 130°C, Class H 180°C)

          - C: Class C solid insulation (resistance to electrical tracerisation)

      Energy efficiency class code words:

          - 1 level: no-load loss ≤ 70% of standard value

          - Class 2: ≤85% of standard value

          - IE4: the highest level of international energy efficiency (efficiency ≥ 99%)

IV. Model Deciphering Practice

      Case 1: S13-M-200/10

          - S: three-phase

         - 13: 13th generation design

         - M: fully sealed structure

         - 200: 200kVA

         - 10: 10kV high voltage side

      Case 2: SCBH15-1000/10-NX2

          - SCBH: three-phase epoxy cast fireproof type

          - 15: amorphous alloy core

          - 1000: 1000kVA

          - NX2: double noise reduction design (noise ≤ 45dB)

      Case 3: DSSZ11-50000/220-TH

          - D: Single-phase

          - SSZ: three-winding on-load voltage regulation

          - 11: 11th generation

          - 50000: 50000kVA

          - 220: 220kV

          - TH: Specialised for hot and humid climates

          The State Grid 2023 sampling found that the misinterpretation of the model number led to equipment selection errors accounted for 23%. When we see "SCB14-1250/10-AN/F" in the parameter table, this string of code is not only a product identification, but also a concentrated history of electrical engineering - from material technology to heat dissipation design, each character tells the story of technological evolution.