A power transformer is electrical equipment that converts alternating current (AC) energy of a certain voltage into AC energy of different voltages based on the principle of electromagnetic induction and mutual inductance. Classified by cooling medium, it mainly includes dry-type transformers and oil-immersed transformers. Among the commonly used models in industrial and civil scenarios, the 315 kva distribution transformer and 33kv to 415v transformer are widely applied due to their stable performance. However, like all electrical equipment, they face fire and explosion risks, so mastering fire and explosion prevention technologies is crucial. JINSHANMEN TECHNOLOGY CO., LTD, a professional manufacturer of power transmission and distribution equipment, has accumulated rich experience in ensuring the safety of transformers such as the 315 kva distribution transformer and 33kv to 415v transformer during production and practice.
I. Fire Hazards of Power Transformers
A power transformer consists of a complete closed magnetic circuit composed of core columns or yokes, and windings made of insulated copper or aluminum wires, forming the primary and secondary windings of the transformer. Except for small-capacity dry-type transformers, most transformers (including the 315 kva distribution transformer and 33kv to 415v transformer used in many projects) adopt oil-immersed natural cooling mode, where insulating oil serves as insulation between windings and a cooling medium.
The flash point of insulating oil in transformers is approximately 135℃, which is easy to evaporate and burn, and can form an explosive mixture when mixed with air. The insulating gaskets and supports inside the transformer are mostly made of organic combustible materials such as cardboard, cotton yarn, cloth, and wood. For example, a 1000kVA transformer uses about 0.012m³ of wood, 40kg of paper, and 1t of insulating oil. For the 315 kva distribution transformer, although the consumption of combustible materials is smaller, the fire risk cannot be ignored.
Once overload or short circuit occurs inside the transformer (such as the 33kv to 415v transformer in the power conversion process), combustible materials and oil will decompose, expand, and even vaporize under the action of high temperature, electric sparks, or electric arcs, causing the internal pressure of the transformer to increase sharply. This may lead to the explosion of the transformer shell, a large amount of insulating oil spraying and burning, and the burning oil flow will further expand the fire hazard.

II. Safety Settings of Power Transformers
According to the requirements of Code for Fire Protection Design of Buildings, the safety settings of power transformers (including the 315 kva distribution transformer and 33kv to 415v transformer) shall comply with the following requirements:
Fire resistance rating requirement: The fire resistance rating of oil-immersed transformer rooms and high-voltage power distribution device rooms shall not be lower than Grade II. Other fire protection designs shall be implemented in accordance with the relevant provisions of codes such as Code for Fire Protection Design of Fossil-Fired Power Plants and Substations GB 50229.
Independent construction principle: Rooms for oil-immersed power transformers, high-voltage capacitors filled with flammable oil, and multi-oil switches should be built independently. When it is really difficult, they can be arranged adjacent to civil buildings, but firewalls shall be used for separation, and they shall not be adjacent to densely populated places. This requirement is particularly important for the 33kv to 415v transformer used in commercial and residential areas.
Layout restriction in dangerous areas: Power transformation and distribution stations shall not be set in Class A or B workshops or built adjacent to them, and shall not be set in hazardous areas of explosive gas or dust environments. For 10kV and below power transformation and distribution stations dedicated to Class A and B workshops, they can be built adjacent to one side when separated by a firewall without door and window openings, and shall comply with the relevant provisions of current national standards such as Code for Design of Electrical Installations in Explosive Atmospheres GB 50058. When the distribution station of a Class B workshop must have windows on the firewall, sealed and fixed Class A fire windows shall be set.
Fire separation distance: The fire separation distance between multi-storey civil buildings and power transformation and distribution stations shall comply with the provisions of Code for Fire Protection Design of Buildings. The fire separation distance between 10kV and below box-type transformers and buildings shall not be less than 3.00m. The 315 kva distribution transformer often used as a box-type transformer shall strictly abide by this distance requirement.
Special requirements for indoor arrangement: When rooms for oil-immersed power transformers, high-voltage capacitors filled with flammable oil, and multi-oil switches have to be arranged in civil buildings due to conditions, they shall not be arranged on the upper floor, lower floor, or adjacent to densely populated places, and shall comply with the following provisions: The transformer room shall be set on the first floor or the basement floor adjacent to the outer wall;
All doors of the transformer room shall directly lead to the outdoors or safe exits; above the opening parts of the outer wall, a non-combustible fire canopy with a width of not less than 1.0m or a window sill wall with a height of not less than 1.20m shall be set;
The transformer room shall be separated from other parts by a non-combustible partition wall with a fire resistance limit of not less than 2.00h and a non-combustible floor slab with a fire resistance limit of not less than 1.50h. No openings shall be opened on the partition wall and floor slab; when doors and windows must be opened on the partition wall, Class A fire doors and windows shall be set;
A non-combustible wall with a fire resistance limit of not less than 2.00h shall be used to separate transformer rooms from each other and transformer rooms from distribution rooms;
Oil-immersed power transformer rooms, multi-oil switch rooms, and high-voltage capacitor rooms shall be equipped with facilities to prevent oil spillage. An accident oil storage facility that can store all the oil of the transformer shall be set under the oil-immersed power transformer;Fire alarm devices shall be installed;Fire-fighting facilities suitable for the capacity of the oil-immersed transformer and the scale of the building shall be installed.
According to Code for Fire Protection Design of Buildings, water mist fire extinguishing systems are recommended for industrial and mining enterprise oil-immersed transformers with a single capacity of 40MVA and above, power plant oil-immersed transformers with a single capacity of 90MVA and above, independent substation oil-immersed transformers with a single capacity of 125MVA and above, and high-voltage capacitor rooms and multi-oil switch rooms filled with flammable oil set in high-rise civil buildings. Fine water mist fire extinguishing systems can be used for indoor oil-immersed transformers, high-voltage capacitor rooms filled with flammable oil, and multi-oil switch rooms.

III. Fire and Explosion Prevention Measures for Power Transformer Ontology
Prevent overload operation: Long-term overload operation will cause the winding to heat up, gradually aging the insulation, resulting in inter-turn short circuit, phase-to-phase short circuit, ground short circuit, and oil decomposition. For transformers of different models such as 315 kva distribution transformer and 33kv to 415v transformer, it is necessary to match the load reasonably according to their rated capacity.
Ensure the quality of insulating oil: If the insulating oil of the transformer is of poor quality or contains too many impurities and moisture during storage, transportation or operation and maintenance, its insulation strength will be reduced. When the insulation strength decreases to a certain value, the transformer will short circuit, causing electric sparks, electric arcs or dangerous temperatures. Therefore, the oil quality of the operating transformer (especially the oil-immersed 315 kva distribution transformer) should be tested regularly, and the unqualified oil should be replaced in time.
Prevent aging and damage of iron core insulation: Aging of iron core insulation or damage of clamping bolt bushings will cause large eddy currents in the iron core, leading to long-term heating of the iron core and insulation aging. This problem is also likely to occur in the 33kv to 415v transformer that has been in operation for a long time, so regular inspection is required.
Prevent insulation damage during maintenance: When lifting the core during transformer maintenance, attention should be paid to protecting the windings or insulating bushings. If scratches or damages are found, they should be handled in time to avoid safety hazards. This maintenance requirement is applicable to all transformers including the 315 kva distribution transformer.
Ensure good contact of conductors: Poor contact at the internal joints of the winding, connection points between windings, joints leading to high and low voltage side bushings, and various fulcrums on the tap changer will cause local overheating, damage insulation, and cause short circuits or open circuits. The high-temperature electric arc generated at this time will decompose the insulating oil, produce a large amount of gas, and increase the pressure inside the transformer. If the pressure exceeds the protection setting value of the gas relay and does not trip, an explosion will occur.
Prevent lightning strikes: The power supply of power transformers generally comes from overhead lines, which are vulnerable to lightning strikes, and the transformer will be burned due to insulation breakdown. The grounding wire of the lightning arrester should be connected to the low-voltage neutral point of the transformer and the grounding bolt of the oil tank for grounding. For 3~10kV Y/YO or Y/Y grounded distribution transformers in lightning-prone areas, to prevent lightning waves from intruding from the low-voltage side, a set of lightning arresters should be installed on the low-voltage side. A valve-type lightning arrester should also be installed when the low-voltage side neutral point is not grounded.
Reliable short-circuit protection: When a short circuit occurs in the transformer winding or load, the transformer will bear a large short-circuit current. If the protection system fails or the protection setting value is too large, the transformer may be burned. Therefore, a reliable short-circuit protection device must be installed. This is a necessary safety guarantee for the 33kv to 415v transformer in the power supply system.
Maintain good grounding: For low-voltage systems using protective neutral grounding, the low-voltage side neutral point of the transformer should be directly grounded. When the three-phase load is unbalanced, current will appear on the neutral line. When this current is too large and the contact resistance is large, high temperature will appear at the grounding point, igniting surrounding combustible materials. The grounding resistance of transformers with a capacity of 100kVA or less should not exceed 10Ω.
Prevent overheating: The temperature change of the transformer should be monitored during operation. If the transformer winding conductor is Class A insulation, its insulator is mainly paper and cotton yarn. The temperature has a great impact on the insulation and service life. For every 8℃ increase in temperature, the insulation life will be reduced by about 50%. The service life of the transformer is about 20 years when operating at normal temperature (90℃); if the temperature rises to 105℃, the service life is 7 years; if the temperature rises to 120℃, the service life is only 2 years. Therefore, when the transformer is in operation, good ventilation and cooling must be maintained. For transformers with large heat generation such as the 315 kva distribution transformer, forced ventilation can be adopted if necessary to reduce the temperature rise of the transformer.
Equip with appropriate fire-fighting facilities: The transformer room should be equipped with corresponding fire-fighting facilities, such as detection and alarm equipment such as cable-type linear fixed-temperature fire detectors, automatic fire extinguishing systems such as carbon dioxide or water mist, and emergency lighting systems. The lines of fire-fighting facilities and equipment can be made of copper-core sheathed mineral insulated, high-temperature resistant, fire-resistant cables or other fire-resistant cables to meet fire-fighting requirements.
Regular inspection and maintenance: The operating transformer should be inspected and maintained regularly, including checking whether the sound, oil level, grounding, thermometer protection device, bushing and the overall cleanliness of the transformer are in good condition and normal, so as to detect hidden dangers early and deal with them in time.
About JINSHANMEN TECHNOLOGY CO., LTD
As a professional manufacturer of power transmission and distribution equipment, JINSHANMEN TECHNOLOGY CO., LTD has always taken product safety as the core, and strictly implements fire and explosion prevention standards in the production of transformers such as 315 kva distribution transformer and 33kv to 415v transformer. The company mainly produces oil immersed power transformers, dry-type power transformers, oil immersed three-dimensional coiled power transformers, dry-type three-dimensional coiled power transformers, mining explosion-proof dry-type transformers, mining explosion-proof mobile substations, amorphous alloy power transformers, on load capacity regulating power transformers, locomotive dry-type transformers, as well as prefabricated substations, modular substations, wind energy box type substations, high and low voltage switchgear and other transmission and distribution equipment. With advanced production technology and strict quality control system, JINSHANMEN TECHNOLOGY provides reliable and safe power transmission and distribution equipment solutions for global customers.