Transformers are one of the key electrical equipment in power distribution stations. Among them, oil-immersed transformers are widely used in various power transmission scenarios due to their excellent dielectric strength, strong heat transfer performance, and economical engineering cost, which successfully solve the problems of large-space heat dissipation and high-voltage insulation of transformers. In particular, the 500 kva oil filled transformer, as a common type of oil-immersed transformer in industrial and civil fields, often faces oil leakage problems during long-term operation. This problem not only troubles the stable operation of the 500 kva power transformer, but also seriously endangers the safe operation of various transformers, which must attract the attention of industry practitioners.
Transformer oil leakage poses multiple serious threats to the safe operation of equipment: first, if the transformer leaks oil for a long time or leaks a lot, it will lead to insufficient oil volume. When the oil level drops too much during operation, it may cause false action of gas protection; if the oil leakage is serious and the internal windings are exposed, it will cause insulation damage, and even thermal breakdown accidents, leading to transformer shutdown and affecting the reliable supply of electricity. Second, oil leakage is easy to cause moisture intrusion, resulting in internal dampness of the transformer and accelerated equipment aging. Third, oil leakage parts are easy to adhere to dust, forming a large area of oil stains, which not only affects the appearance of the equipment, but also brings inconvenience to subsequent maintenance. Fourth, the leaked transformer oil not only causes resource waste, but also pollutes the surrounding environment. Therefore, whether it is a 500 kva power transformer or other types of oil-immersed transformers, oil leakage problems need to be investigated and handled in a timely manner.

I. Analysis of Causes of Transformer Oil Leakage
The causes of transformer oil leakage are complex and diverse, which are related to many factors such as the manufacturing quality of parts, operating environment, installation quality, and service life. Combining the years of industry practice of JINSHANMEN TECHNOLOGY, summarizing the oil leakage cases of various transformers (including 500 kva power transformers and 500 kva oil filled transformers), the main causes can be divided into the following 6 points:
1. Aging of Sealing Gaskets
Most transformer oil leaks occur at the connection between the oil tank and parts, among which more than 90% of the oil leakage problems are caused by the aging of sealing gaskets. The core of the quality of sealing parts lies in their oil resistance. Sealing parts with poor oil resistance age faster, especially in high-temperature environments, the aging speed will be greatly accelerated. The temperature of the transformer can reach more than 70℃ during operation. Under the long-term effect of high temperature, the sealing parts are prone to aging and deformation, and finally fail, leading to oil leakage. This problem is particularly common in 500 kva oil filled transformers that have been in operation for a long time, and the sealing gaskets need to be regularly inspected and replaced.
2. Harsh Operating Environment
Most transformers operate outdoors with harsh environment and large temperature difference. The outdoor temperature can reach 42℃ in summer and as low as -15℃ in winter. In addition to the heat generated by the transformer itself during operation, long-term thermal expansion and contraction will cause the sealing gasket to lose elasticity, leading to oil leakage. For 500 kva power transformers installed outdoors, the impact of environmental factors is more obvious, and protective measures need to be taken to reduce the loss of equipment caused by the environment.
3. Poor Welding Quality
Oil-immersed transformers are based on steel plate welded shells and are a collection of various welds and connections. During the production process, the oil tank has many welding points, long weld seams, and high welding difficulty. The quality of welding materials, welding methods, and the technical level of welders will all affect the welding quality. For example, the total number of welding points of a large transformer can reach more than 70. Defects such as air holes, sand holes, false welding, and poor contact in the weld seams will gradually appear during the operation of the equipment, leading to oil leakage. When producing 500 kva oil filled transformers, JINSHANMEN TECHNOLOGY strictly controls the welding process, reduces welding defects, and reduces the risk of oil leakage from the source.
4. Substandard Machining Process
Non-compliance with the specified machining process and process will directly lead to oil leakage problems. Too loose or too tight tightening during assembly, unclean or uneven sealing gaskets, uneven flange connections of parts, uneven stress on the bolts around the sealing gaskets caused by human factors during installation, and deformation and displacement of flange joints (mostly occurring at the gas relay and the connection between the radiator and the main body) will all cause oil leakage. In addition, due to poor installation quality and uneven stress at the connection of the bushing of large transformers, oil leakage is also prone to occur, which needs to be focused on during the installation of 500 kva power transformers.
5. Insufficient Technical Level of Maintenance Personnel
At present, some enterprises have a personnel gap in the front line of maintenance. Due to the limitation of personnel and equipment, most transformer maintenance relies on external cooperation teams. Some external cooperation personnel have insufficient sense of responsibility. During maintenance, they do not strictly follow the technical specifications, do not carefully check the cause of oil leakage, and do not conduct sufficient leak detection or the negative pressure time is insufficient after maintenance, resulting in the oil leakage defect still existing after maintenance, or even worsening the fault. JINSHANMEN TECHNOLOGY has a professional maintenance team, which can provide professional maintenance services for various equipment such as 500 kva power transformers and 500 kva oil filled transformers to ensure maintenance quality.
6. External Damage
During the transportation and hoisting of the transformer, if the parts are hit, the radiators and other pipelines are distorted by external force, or other parts are damaged and deformed, the welding joints are cracked, and hidden defects such as cracks appear, after the equipment is put into operation, with the increase of temperature and internal pressure, these defects will gradually expand, leading to oil leakage. Therefore, the transportation and hoisting process of equipment such as 500 kva oil filled transformers must strictly follow the operating specifications and take protective measures.

II. Solutions to Transformer Oil Leakage
Before handling transformer oil leakage, it is necessary to carefully analyze and identify the cause of leakage and the exact leakage point. For the oil stains on the equipment surface, first clean them with a small flat shovel and steel wire brush, then clean them with cleaning agents such as tetrachloroethylene, acetone, and alcohol, rinse them with clean water, and wipe them repeatedly with a clean cloth to ensure that the leakage point is accurately found, laying a foundation for subsequent treatment. Combining the practical experience of JINSHANMEN TECHNOLOGY, there are mainly the following 2 solutions for different oil leakage situations:
1. Using Welding to Treat Transformer Oil Leakage
If oil leakage is found in the upper part of the transformer oil tank, only a small amount of oil needs to be drained for welding treatment; if oil leakage is found in the lower part of the oil tank, due to the large waste of core lifting and oil draining and the limitation of on-site conditions, oil-carrying welding treatment can be adopted. Oil-carrying repair welding should be carried out when the oil leakage is not significant. Otherwise, vacuum oil draining method should be used to create negative pressure before welding. The vacuum degree of negative pressure should not be too high, which should be equal to the internal and external pressure to avoid inhaling molten iron.
During repair welding, the oil stains on the welding part must be completely cleaned, preferably rinsed with alkaline water and then dried; attention should be paid to preventing welding penetration and fire during the welding process, and the welding part must be below the oil level; intermittent and rapid spot welding should be adopted, and the arc ignition time should be controlled within 10s~20s, and long-term continuous welding is strictly prohibited. When repairing welding holes with serious oil leakage, they can be blocked with iron wire or riveted before welding; when welding near the sealing rubber gasket or other vulnerable parts, cooling and protective measures must be taken to avoid damaging the parts. This method is suitable for the treatment of oil leakage at the welding parts of various oil-immersed transformers such as 500 kva power transformers and 500 kva oil filled transformers.
2. On-site Rapid Bonding and Plugging Method for Transformer Oil Leakage
Sorel carbon nano-polymer material adopts cold welding bonding technology, which has the characteristics of strong bonding force and weather resistance, and has comprehensive mechanical properties such as elastic deformation of metal. On the premise of ensuring safety, it can realize on-line treatment of transformer oil leakage without shutdown, which greatly reduces the loss caused by equipment shutdown. This method is simple to operate and efficient, and is suitable for oil leakage at the sealing parts of various transformers, especially for on-site rapid repair of common models such as 500 kva oil filled transformers, which can quickly solve the oil leakage problem and restore the normal operation of the equipment.
JINSHANMEN TECHNOLOGY CO., LTD has always taken high quality and high reliability as the core. When producing various transformers (including 500 kva power transformers and 500 kva oil filled transformers), it strictly controls every process, from raw material procurement, production and processing to finished product inspection, and follows industry standards throughout the process, effectively reducing the incidence of common faults such as oil leakage. At the same time, the company provides professional after-sales maintenance services to solve various problems during the operation of equipment for customers, helping customers achieve stable and safe operation of power equipment.