Ⅰ. Introduction
Neutral point grounding is one of the most critical safety and operational specifications for high-voltage power transformers, especially for 110kV and above power grid equipment. Reasonable neutral point grounding configuration can effectively suppress switching overvoltage, avoid insulation breakdown, and ensure the accurate action of power system protection devices. In industrial and commercial power distribution scenarios, both oil filled distribution transformer and large-capacity power equipment rely on standardized neutral grounding strategies to maintain long-term operational stability.
As a widely used medium and large-capacity power distribution device, the 750 kva 3 phase transformer is frequently deployed in factory parks, commercial complexes and supporting power grids. Mastering neutral point grounding rules is essential to eliminate hidden overvoltage dangers during equipment commissioning, shutdown and switching operations.
JINSHANMEN TECHNOLOGY CO., LTD is a professional manufacturer of full-series power transmission and distribution equipment. The company mainly produces oil immersed power transformers, dry-type power transformers, oil immersed three-dimensional coiled power transformers, dry-type three-dimensional coiled power transformers, mining explosion-proof dry-type transformers, mining explosion-proof mobile substations, amorphous alloy power transformers, on load capacity regulating power transformers, locomotive dry-type transformers, as well as prefabricated substations, modular substations, wind energy box type substations, high and low voltage switchgear and other transmission and distribution equipment. With in-depth research on power system operation specifications, we provide standardized grounding and protection configuration for oil filled distribution transformer, 750 kva 3 phase transformer and all supporting products to adapt to complex grid operating conditions.

Ⅱ. Core Principle: Why Neutral Point Must Be Grounded During Transformer Switching
1. Overvoltage Risk of Ungrounded Neutral Point
During the closing and opening operation of high-voltage circuit breakers, phase separation or non-synchronous switching frequently occurs. If the transformer neutral point remains ungrounded, the floating neutral potential will produce dangerous overvoltage, which directly endangers winding insulation. This hidden danger universally exists in all high-voltage power distribution equipment, including the 750 kva 3 phase transformer commonly used in industrial power grids.
For power-receiving transformers with power supply on one side, an ungrounded neutral point will cause the neutral-to-ground voltage to reach the full phase voltage under non-full-phase switching conditions. Meanwhile, the capacitive coupling between high-voltage and low-voltage windings will generate transferred overvoltage from the high-voltage side to the low-voltage side. In severe cases, resonance overvoltage will be triggered, causing irreversible damage to transformer insulation.
For power-sending transformers with low-side power sources, ungrounded neutral points bring more severe risks. Before grid connection, single-phase grounding faults on the high-voltage side will raise the neutral point potential to phase voltage. During asynchronous grid connection, the neutral point floating voltage can reach twice the phase voltage, and the unclosed phase voltage can reach 2.73 times the phase voltage, easily causing insulation flashover and breakdown accidents.
2. Industry Operation Specification
In China's 110kV and above power grid system, neutral-point direct grounding is the mainstream operation mode. To ensure the sensitivity of zero-sequence protection, the neutral grounding switch of main transformers is usually open during normal operation. However, the neutral grounding switch must be closed during all commissioning and shutdown operations to suppress switching overvoltage and protect winding insulation.
Ⅲ. Neutral Point Gap Grounding Protection Configuration
1. Protection Composition and Action Logic
Transformer neutral point gap grounding protection adopts a parallel configuration of zero-sequence current relays and zero-sequence voltage relays, with a fixed 0.5s delay. When a system grounding fault occurs and the discharge gap breaks down and discharges, the zero-sequence current detected by the dedicated gap current transformer triggers the current relay action. If the gap does not discharge, the zero-sequence voltage relay responds to system unbalanced overvoltage to complete fault protection.
For intermittent arc grounding faults, the common time element of gap protection is designed without mid-return function, which ensures reliable and consistent protection action during continuous arc faults and avoids protection refusal or misoperation.
Ⅳ. Grounding Requirements for No-Load Transformer Energization
Energizing no-load transformers without neutral point grounding is a major on-site operational hazard. Floating neutral potential will cause three typical risks: phase-level neutral-to-ground overvoltage, high-low voltage capacitive transferred overvoltage, and resonant overvoltage. All three abnormal voltages will impact the insulation system of oil filled distribution transformer and other power equipment, accelerating insulation aging or causing direct breakdown.
Therefore, it is a mandatory on-site specification that the neutral point must be reliably grounded before energizing any no-load high-voltage transformer.

Ⅴ. Overall Arrangement Principles of Transformer Neutral Grounding
The core principle of neutral point grounding arrangement is to keep the substation zero-sequence impedance stable and avoid large fluctuations in zero-sequence current distribution, which ensures the coordination and accuracy of power grid protection settings. The specific arrangement rules are classified according to the number of transformers and bus operation modes.
1. Single Transformer Substation
The transformer neutral point shall be directly grounded in normal operation. Protection settings are calculated based on the grounded operating state. During transformer maintenance and outage, adjust protection settings or disable corresponding protection segments according to special operating specifications.
2. Two or More Transformers
Only one transformer neutral point is kept directly grounded under normal operation. When the grounded transformer is out of service, switch another ungrounded transformer to direct grounding state to maintain stable zero-sequence impedance. If two grounding points are required for special reasons, replace the grounding point in time when any grounded transformer trips.
3. Double Bus Operation with Three or More Transformers
Maintain two neutral grounding points respectively on different buses to balance zero-sequence impedance distribution. When one grounding point fails, replace it with an ungrounded transformer on the corresponding bus. If cross-bus replacement cannot be realized, classify as special operation and adjust protection parameters.
4. Special Scenario Supplement
When short-line maintenance causes changes in zero-sequence current distribution, appropriately increase the number of grounded transformers to compensate for impedance changes. Autotransformers and transformers with special insulation level requirements must operate with permanently grounded neutral points.
Ⅵ. Standard Operation for Neutral Grounding Switch Switching
1. Operation Sequence
All neutral point grounding switch switching must follow the ground first, break later principle to ensure the power grid has continuous grounding points without floating dead zones. The standard steps are as follows: first, close the standby neutral grounding isolator; second, open the original working grounding isolator; finally, switch the zero-sequence protection configuration to the newly grounded transformer.
2. Theoretical Basis for "Close First, Break Later"
High-voltage main transformers adopt split-phase circuit breakers, which are prone to non-full-phase closing or breaking during operation. If the neutral point grounding is disconnected first, the floating neutral point will generate severe zero-sequence overvoltage under non-synchronous and non-full-phase conditions, which will be coupled to the low-voltage side and damage insulation. The "close first, break later" method maintains continuous grounding constraints, effectively limiting transient overvoltage.
In terms of protection logic, this operation ensures zero-sequence protection or gap protection is always in active operation, avoiding protection blank zones and ensuring continuous safety constraints for the transformer and the entire busbar system.
Ⅶ. Conclusion
Transformer neutral point grounding is not only a basic grid connection condition, but also a core safety barrier to suppress switching overvoltage, prevent insulation damage, and ensure protection accuracy. All no-load energization, shutdown maintenance and grounding switching operations must comply with standardized procedures to eliminate floating neutral overvoltage risks. Reasonable grounding layout and standardized operation are essential guarantees for the long-term stable operation of power distribution equipment.
JINSHANMEN TECHNOLOGY CO., LTD adheres to strict power grid operation standards. We optimize grounding and protection matching for oil filled distribution transformer, 750 kva 3 phase transformer and all series of power distribution equipment, providing safe, compliant and reliable power equipment solutions for global power distribution projects.
